You are viewing the technical directory listing for 24V Power Supply Design for Industrial Automation. This engineering resource is curated under our Rockwell Automation division to support automation specialists, control systems engineers, and manufacturing technicians looking for verified reference materials.

🔍 Contextual Abstract & Technical Scope

Share Summary:LinkedInEmail

A 24V power supply in an automation system has to support continuous loads while responding to events such as motor starts, capacitor charging and branch-circuit faults. The Rockwell Automation 1606-XLS480E and 1606-XLS480EC are single-phase units designed for these conditions, combining a 480W continuous output with short-term reserve capacity and built-in status monitoring. For engineers and system integrators, understanding those operating limits is essential to selecting, wiring and protecting the supply appropriately.

24V power supply capacity: continuous and short-term loads

The units provide a nominal 24V DC output, adjustable from 24V to 28V. At 24V, rated continuous output is 20A, or 480W. At 28V, continuous current is 17A while output power remains 480W. This distinction matters when selecting the output voltage: raising voltage does not increase the rated continuous wattage.

For brief load peaks, the supply’s Power-Boost function can provide up to 30A at 24V, equivalent to 720W, for typically four seconds. The specified boost duration is 3.5 to 4.5 seconds under the stated conditions. This temporary capacity can help with loads that draw elevated current during startup, but it is not a substitute for sizing the supply to the application’s continuous demand.

For recurring pulses, check three conditions: peak power must remain below 150% of nominal power, pulse duration must stay within the permitted boost time, and average output current must remain within the continuous rating. Excessive average loading can eventually cause thermal shutdown. Ambient temperature and installation altitude can also reduce the available output capacity.

Input flexibility and installation considerations

The AC input is rated for a nominal 100–240V range, with continuous operation specified from 85V to 276V AC. The product also accepts DC input: the nominal range is 110–300V DC, with continuous operation specified from 88V to 375V DC. This broad input capability can simplify integration where the available supply varies, but the wiring method must match the selected input type and the manufacturer’s instructions.

Active power-factor correction is included. Typical power factor at full load is 0.95 at 120V AC and 0.90 at 230V AC. The supply also uses active inrush-current limitation; typical inrush is 9A peak at 120V AC and 7A peak at 230V AC. These values can inform supply and protection planning, but they do not replace a review of applicable electrical codes or the characteristics of the complete circuit.

The unit is designed for convection cooling and mounts on a 35mm DIN rail. Keep the ventilation grid clear, observe the recommended installation clearances, and account for heat from nearby equipment. The operating temperature range is -25°C to +70°C, with output derating above +60°C at 12W per °C. Above 2,000m altitude, the output or ambient temperature must also be derated as specified in the product documentation.

Monitoring, overload behavior and protection

A green DC-OK LED, red overload LED and DC-OK relay contact provide local and remote indications of supply status. The relay monitors the output voltage produced by the power supply itself. It closes when the output reaches its adjusted voltage and opens when voltage falls more than 10% below that level, subject to the specified signal response. This gives control and supervisory systems a way to detect a supply condition without relying only on a visual inspection.

Electronic protection covers overloads, no-load operation and short circuits. Under sustained overload, the supply can deliver output current for up to about four seconds before reducing output power to nearly zero for approximately 17 seconds and then attempting to restart. If the overload remains, this cycle repeats. The overload LED indicates the condition, with the product documentation describing its behavior during the rest period.

Internal output capacitors can provide brief peak current for demanding loads, including solenoids, contactors and downstream circuit breakers. That peak current can cause a temporary output-voltage dip; for example, the specification gives a typical dip from 24V to 17.5V for an 80A, five-millisecond event. Engineers should consider whether connected equipment can tolerate the resulting voltage change, rather than treating peak-current capability as an additional continuous rating.

Designing parallel, redundant and branched systems

Multiple units can be connected in parallel to increase output power or provide redundancy. For parallel operation, use supplies from the same XLS series and adjust their output voltages to approximately the same value, within ±500mV. In a redundant arrangement, use separate input fuses for each supply and monitor each unit’s DC-OK status. The documentation notes that a redundancy module can provide output decoupling to address a failure mode that a simple parallel connection does not cover.

Plan output distribution as carefully as the supply itself. Daisy-chaining is permitted only while current through any one terminal pin does not continuously exceed 20A; use distribution terminals when it would. When adding branch circuit protection, select DC-rated breakers where required and consider wiring resistance, loop impedance and breaker trip characteristics. The product’s application guidance reports typical test results, not a guarantee that a particular breaker will trip under every installation condition.

Conclusion: size for the real operating profile

These 24V supplies combine a 480W continuous rating with brief overload capacity, wide AC and DC input ranges, and status monitoring. Applying those features well means checking steady-state and peak loads separately, allowing for temperature and altitude derating, and following the requirements for earthing, wiring, cooling and branch protection. Those design checks help ensure the power supply fits the machine’s electrical and operational needs.